1210-1S-230

Bourns Inc. 1210-1S-230

Part No:

1210-1S-230

Manufacturer:

Bourns Inc.

Datasheet:

1210 Series

Package:

-

ROHS:

AINNX NO:

4950119-1210-1S-230

Description:

415 V ac 100kA 1210 1 Pole Protector,DIN Rail Mounting

Products specifications
  • Factory Lead Time
    12 Weeks
  • Mount
    DIN Rail
  • Mounting Type
    DIN Rail
  • Housing Material
    Plastic
  • Voltage Rated

    RATED voltage is the voltage on the nameplate - the "design point" for maximum power throughput and safe thermal operation.

    415V
  • Operating Temperature

    The operating temperature is the range of ambient temperature within which a power supply, or any other electrical equipment, operate in. This ranges from a minimum operating temperature, to a peak or maximum operating temperature, outside which, the power supply may fail.

    -50°C~85°C
  • Series
    1210
  • Published
    2010
  • Part Status

    Parts can have many statuses as they progress through the configuration, analysis, review, and approval stages.

    Active
  • Moisture Sensitivity Level (MSL)
    1 (Unlimited)
  • Termination
    Screw
  • Type
    Type 2, Type 4
  • Max Operating Temperature

    The Maximum Operating Temperature is the maximum body temperature at which the thermistor is designed to operate for extended periods of time with acceptable stability of its electrical characteristics.

    85°C
  • Min Operating Temperature
    -50°C
  • Voltage - Rated DC
    275V
  • Depth
    67mm
  • Current Rating

    Current rating is the maximum current that a fuse will carry for an indefinite period without too much deterioration of the fuse element.

    20kA
  • Base Part Number
    1210
  • Voltage - Rated AC
    230V
  • Approval Agency
    CE, CSA, UL
  • Number of Poles
    1
  • Max Surge Current

    Surge current is a peak non repetitive current. Maximum (peak or surge) forward current = IFSM or if(surge), the maximum peak amount of current the diode is able to conduct in forward bias mode.

    100kA
  • Form
    Module Only
  • Overload Protection

    Overload protection is a protection against a running overcurrent that would cause overheating of the protected equipment. Hence, an overload is also type of overcurrent. Overload protection typically operates on an inverse time curve where the tripping time becomes less as the current increases.

    None
  • Voltage - Continuous Operating (Max) (MCOV)
    275VAC
  • Current - Discharge (Nom) (8/20μS)
    20kA
  • Features
    Remote Signaling Contacts, Thermally Protected
  • Current - Discharge (Max) (8/20μS)
    100kA
  • Current - Short Circuit Rating (SCRR)
    100kA
  • Voltage - Protection Rating (VPR)
    900V
  • Voltage - Protection Level (VP) (2416)
    1.25kV
  • Height
    99mm
  • Length
    67mm
  • Width
    18mm
  • REACH SVHC
    No SVHC
  • RoHS Status

    RoHS means “Restriction of Certain Hazardous Substances” in the “Hazardous Substances Directive” in electrical and electronic equipment.

    ROHS3 Compliant
  • Lead Free
    Lead Free
  • Ratings
    IP20
0 Similar Products Remaining